MANDÍK MCS-B Electronic Control System

MANDÍK MCS-B Electronic Control System

A sophisticated, scalable monitoring and control system for motorized fire dampers. Capable of managing up to 240 dampers, it features a central touchscreen unit, automatic module detection via RS-485 communication, and supports open protocols for seamless integration into building management and fire safety systems.

Product Description

Key Features & Benefits

  • Centralized Touchscreen Control

    High-resolution touchscreen provides intuitive monitoring and control of all dampers.

  • Universal Actuator Compatibility

    Supports all standard 24V AC/DC and 230V AC damper actuators.

  • Scalable Architecture

    Manages up to 240 dampers across two zones with automatic module detection.

  • Long-Range Communication

    RS-485 bus supports distances up to 1200m per zone without a repeater.

  • Cloud & Remote Access

    Optional Wi-Fi for cloud access, email alerts, and remote monitoring via external PC.

  • Integrated Safety Monitoring

    Modules can connect smoke detectors and thermoelectric trip devices for enhanced safety.

Technical Specifications

System Capacity

Max Dampers: 240. Max Modules: 120 UFC modules across 2 zones.

Power & Actuator Support

Actuator Voltages: 24V AC/DC, 230V AC. Module: UFC24-2 (2 dampers per module).

Communication & Protocols

Bus: RS-485. Protocols: Modbus RTU, BACnet MS/TP. Topology: Bus, 2 zones.

System Dimensions

Max Distance: 1200m between central unit and module (per zone, no repeater).

Central Unit Features

High-res touchscreen, automatic module detection, event logging, test functions.

Module Features (UFC24-2)

Address by DIP switch, end-switch time measurement, 1 smoke detector & 1 thermal trip input.

Installation & Integration

Modular Bus Wiring

Simple RS-485 bus wiring in daisy-chain topology for easy expansion.

Plug-and-Play Detection

Master unit automatically detects all addressed slave modules; no complex configuration.

BMS/BAS Integration

Direct integration via open Modbus RTU or BACnet MS/TP protocols.

Remote Monitoring Setup

Optional Wi-Fi module enables cloud access for email alerts and remote system views.

Automated Testing

Schedule or initiate automatic testing sequences for all dampers from the central unit.

Use Cases

Product brochure